福尼Forney火檢放大器 IDD 9000
雙通道面板安裝(PM)IDD 9000放大器零件#408100-00
單通道面板安裝(PM)IDD 9000放大器零件#408100-50
機(jī)架安裝(RM)IDD 9000放大器–雙通道部件#408120-01
放大器調(diào)整套件零件#408103-01
帶9針連接器的Termiflex /SMARTDisplay?端子*部件號(hào)408106-01
電纜40'(用于IDD)部件號(hào)399854-04
電纜40'(用于UV-4)部件號(hào)399855-04
兼容的火焰探測(cè)器:
IDD-II,過(guò)濾的紅外探測(cè)器,零件號(hào)38321-21
IDD-IIU,未過(guò)濾的紅外檢測(cè)器,零件號(hào)#38321-22
IDD-IIL,褐煤零件的紅外探測(cè)器#38321-23
UV-4,UV管檢測(cè)器零件號(hào)379189-02
*如果使用帶有25針連接的較舊的Termiflex / SMARTDisplay?終端,則需要DB25針至DB9針的適配器(Forney零件號(hào)408107-01)
IDD 9000規(guī)格:
面板安裝:機(jī)架安裝:
尺寸:10 1/2英寸x 7 7/8英寸x 3 7/8英寸(26.6厘米x 20厘米x 9.8厘米)6.5 x 14 x 1.75英寸(155.6 x 355.6 x 44.5毫米)
重量:5磅。 3盎司1磅7盎司
溫度:32°至140°F(0°至60°C)
濕度:5%至95%相對(duì)濕度,無(wú)凝結(jié)
電源要求:120/240 VAC,50/60 Hz @ 12 VA
輸出繼電器額定值(SPDT):125 VAC,250 VAC和30 VDC時(shí)為3 A
每個(gè)通道可使用3個(gè)繼電器(指示燈,主火焰和警報(bào))。
阻燃強(qiáng)度:4-20 mA或0-10 VDC(源)
火焰故障響應(yīng)時(shí)間(FFRT):2.0、3.0或3.8秒
火焰拾取時(shí)間:少于2秒
非易失性RAM:8個(gè)完整的操作配置文件
Forney Flame Detection Amplifier IDD 9000
Dual Channel Panel Mount (PM) IDD 9000 Amplifier Part # 408100-00
Single Channel Panel Mount (PM) IDD 9000 Amplifier Part # 408100-50
Rack Mount (RM) IDD 9000 Amplifier – Dual Channel Unit # 408120-01
Amplifier Adjustment Kit Part # 408103-01
Termiflex/SMARTDisplay with 9-pin connector ? Terminal * Part No. 408106-01
Cable 40 '(for IDD) Part No. 399854-04
Cable 40 '(for UV-4) Part No. 399855-04
Compatible flame detectors:
IDD-II, filtered infrared detector, part number 38321-21
IDD-IIU, unfiltered infrared detector, part number # 38321-22
IDD-IIL, infrared detector of lignite parts # 38321-23
UV-4, UV tube detector part number 379189-02
*If using an older Termiflex/SMARTDisplay with a 25 pin connection ? Terminal, an adapter from DB25 pin to DB9 pin is required (Forney part number 408107-01)
IDD 9000 Specification:
Panel installation: rack installation:
Dimensions: 10 1/2 "x 7 7/8" x 3 7/8 "(26.6 cm x 20 cm x 9.8 cm) 6.5 x 14 x 1.75" (155.6 x 355.6 x 44.5 mm)
Weight: 5 lbs. 3 oz 1 lb 7 oz
Temperature: 32 ° to 140 ° F (0 ° to 60 ° C)contact sale e-mail :njxj888@163.com
Humidity: 5% to 95% relative humidity, no condensation
Power requirements: 120/240 VAC, 50/60 Hz @ 12 VA
Output relay rating (SPDT): 125 VAC, 3 A at 250 VAC and 30 VDC
Each channel can use 3 relays (indicator light, main flame and alarm).
Flame retardant strength: 4-20 mA or 0-10 VDC (source)
Flame fault response time (FFRT): 2.0, 3.0 or 3.8 seconds
Flame pickup time: less than 2 seconds
Non volatile RAM: 8 complete operation configuration files